Operating instructions for the Endress+Hauser RMM621 Application Manager, covering installation, wiring, commissioning, formula editing, and troubleshooting.
The Endress+Hauser RMM621 Application Manager calculates physical variables from values provided by connected sensors. It supports data logging, telecontrol, control, scaled multichannel display, and calculations using stored or freely defined formulae.
Installation is on a top-hat rail in a cabinet, with up to three optional extension cards. The manual covers wiring, local operation, commissioning, formula editing, maintenance, troubleshooting, and technical data.
| Device length | 135 mm (5.31 in) (8TE) |
|---|---|
| Mounting | Top-hat rail as per IEC 60715 |
| Extension card slots | Maximum of three (B, C, D) |
| Venting for extension cards | Air current of at least 0.5 m/s |
| Current input range | 0/4 to 20 mA +10% overreach |
| Maximum input current (standard current input) | 150 mA |
| Input impedance (standard current input) | < 10 Ω |
| Current input accuracy | 0.1% of full scale value |
| Maximum input current (U-I-TC card) | 80 mA |
| PFM and pulse frequency range | 0.01 Hz to 18 kHz |
| Digital input voltage levels | Low -3 to 5 V; high 12 to 30 V |
| RTD measuring current | 500 μA |
It calculates physical variables made available by connected sensors using stored or freely defined formulae.
Yes, formulae can be edited directly at the device or on a PC using ReadWin.
It mounts on a top-hat rail as per IEC 60715 in a cabinet.
Up to three extension cards can be installed in slots B, C, and D.