This quick guide provides EMC-compliant installation instructions for the Danfoss VLT 2800 frequency converter, covering safety, mechanical mounting, and…
This document serves as a quick guide for the installation and commissioning of the Danfoss VLT 2800 frequency converter. It outlines essential safety precautions, including high voltage warnings and requirements for leakage current protection and residual current devices (RCD). The guide emphasizes that it contains only basic information and directs users to the Operation Manual and Design Guide for detailed functional descriptions and advanced examples.
| Leakage current to earth | exceeds 3.5 mA |
|---|---|
| RCD type requirement | Type B-breaker |
| Thermal motor protection default | not enabled |
| Cooling clearance top/bottom | at least 10 cm |
| Cooling clearance side (IP 21) | at least 100 mm |
A Type B-breaker (time-shifted) must be used on the product's supply side.
No, protection against motor overload is not included in the factory settings.
The leakage current to earth from the frequency converter exceeds 3.5 mA.