Danfoss MCD 200 Series Soft Starter Design Guide

This design guide covers the Danfoss MCD 200, MCD 201, and MCD 202 soft starter series, including overview, ratings, installation, and technical data.


Danfoss MCD 200 Series Soft Starter Design Guide - cover page
Brand
Danfoss
Category
Motor
Document type
User Manual
Language
English
Pages
29
File format
PDF
File size
1.1 MB
Published
23 October, 2026
Updated
23 October, 2026
Model
MCD 200
MD5 checksum
ECDEC5B9746A467290856BB233B67043

About this manual

The Danfoss MCD 200 Series comprises two ranges, MCD 201 and MCD 202, which share a common power and mechanical design but offer different functionality. The MCD 201 provides Timed Voltage Ramp (TVR) starting and stopping control, while the MCD 202 provides Current Limit starting control, TVR soft stop, and includes a range of motor protection functions. Both ranges include an integral bypass function to minimize heat dissipation during run.

What's inside

  • MCD 200 Series Overview
  • Description
  • Ratings
  • General Technical Data
  • Mechanical Installation
  • Dimensions and Weights
  • Cable Size
  • Semiconductor Fuses
  • Frequently Asked Questions
  • Fault Finding

Specifications

Mains Supply3 x 200 VAC ~ 440 VAC (+10% / - 15%) or 3 x 200 VAC ~ 575 VAC (+10% / - 15%)
Supply frequency45 Hz - 66 Hz
Control Supply24 VAC/VDC (± 20%) or 110-240 VAC (+10% / - 15%) or 380-440 VAC (+10% / - 15%)
Operating Temperatures-10 °C / + 60 °C
Degree of protectionIP20 for MCD 200-007 to MCD 200-055; IP00 for MCD 200-075 to MCD 200-110
Short Circuit Rated current5 kA for MCD 200-007 to MCD 200-037; 10 kA for MCD 200-045 to MCD 200-110

Frequently asked questions

What is the difference between MCD 201 and MCD 202?

MCD 201 provides TVR starting and stopping control for use with an external motor protection device, while MCD 202 provides Current Limit starting control, TVR soft stop, and includes motor protection functions.

Can the MCD 200 be installed in non-ventilated enclosures?

Yes, the integral bypass function makes the MCD 200 suitable for installation within non-ventilated enclosures without the need for an external bypass contactor.

What are the maximum start current and duration for the MCD 200?

The MCD 200 supports a start current of 400% for 6 seconds.