User manual for the Danfoss VLT Micro Drive FC 51 frequency converter, covering safety, programming, parameters, and troubleshooting.
Danfoss VLT Micro Drive FC 51 is a frequency converter. This manual covers safety instructions, an introduction with ordering type code and abbreviations, programming with MCT-10, LCP 11, and LCP 12, and parameter descriptions and lists.
Parameter groups include operation/display, load/motor, braking, reference/ramp, limits/warnings, digital and analog I/O, controller, communication, special functions, drive information, and data readouts. The manual also includes troubleshooting and an index. This manual is written in Chinese.
| Ground leakage current | Greater than 3.5 mA |
|---|---|
| Wait time before touching | At least 4 minutes |
| RCD type | Class B (delayed) |
| IT mains maximum supply voltage | 440 V |
| Altitude installation | Consult Danfoss Drives above 2 km |
| Low-speed load compensation range | 0-199 % |
| High-speed load compensation range | 0-199 % |
| Slip compensation range | -400 to 399 % |
| Slip compensation time | 0.05-5.00 s (default 0.10 s) |
Wait at least 4 minutes for all ratings.
Only a class B (delayed) RCD can be used.
The default is 0, meaning no password.
The ground leakage current is greater than 3.5 mA.