Cooper Bussmann T Range Medium Voltage DIN Fuses Product Leaflet

Cooper Bussmann leaflet on its T range medium voltage DIN current-limiting fuse-links, covering types, technology, voltage ratings, bases and applications.


Cooper Bussmann T Range Medium Voltage DIN Fuses Product Leaflet - cover page
Brand
Cooper Bussmann
Category
Other Electronics
Document type
Product Leaflet
Language
English
Pages
22
File format
PDF
File size
887 KB
Published
08 November, 2026
Updated
08 November, 2026
MD5 checksum
1472EF686A7E59F7451089BC3AD290F1

About this manual

This leaflet describes Cooper Bussmann medium voltage DIN current-limiting fuse-links, offered as the T range and built to dimensional standard DIN 43625. The fuse-links follow IEC 60282-1, 2005 and are stated to be lead and cadmium free, complying with the RoHS and WEE directives.

The document explains medium voltage fuse technology: the back-up, general purpose and full range types defined in IEC 60282-1, the star-core element construction with granular quartz filler, striker mechanisms and M-effect temperature limitation. It also lists the voltage ranges covered (3.6 kV, 7.2 kV, 12 kV, 17.5 kV, 24 kV and 36 kV), fuse-link bases, applications, a cross-reference, striker force diagrams and the part referencing system.

What's inside

  • Introduction to medium voltage fuse-links
  • Features and Benefits
  • Medium voltage fuse technology
  • Glossary for medium voltage fuse-links
  • Voltage ratings 3.6 kV to 36 kV
  • Fuse-links bases
  • Applications
  • Cross-reference
  • Striker force diagrams
  • Part referencing system

Specifications

Governing standardIEC 60282-1, 2005
Medium voltage range (IEC definition)1 kV to 72.5 kV
Dimensional standardDIN 43625
Standards complied withBS, IEC, DIN and UL
Striker output force, part numbers with sequence "E"80 N, travel 30 mm
Striker output force, part numbers with "S"50 N, maximum travel 26 mm
Typical de-rating in confined space5-20 % depending on application
Melting temperature of silver fuse elements960 °C
Environmental complianceLead and cadmium free (RoHS and WEE directives)

Frequently asked questions

Which international standards do Cooper Bussmann circuit protection solutions comply with?

They comply with the major international standards BS, IEC, DIN and UL.

What is the striker output force on fuse-links with the "E" part number sequence?

Those fuse-links have a spring striker with an output force of 80 N and a travel of 30 mm.

What is the difference between Back-Up, General Purpose and Full Range MV fuses?

Back-Up fuse-links interrupt any current from rated breaking capacity down to a minimum breaking current; General Purpose fuses interrupt all currents that melt the elements within one hour; Full Range fuses interrupt any current below rated breaking capacity that melts the elements satisfactorily.

How is temperature limitation achieved in Cooper Bussmann medium voltage fuses?

M-effect technology is used: a small mass of special low melting point alloy is added to each fuse element, reducing the fuse temperature during operation.

Download PDF (887 KB)