Brainboxes ED-038 Ethernet to digital I/O relay module with 3 digital inputs, 3 Form A relay outputs and +5 to +30 V DC power input.
The Brainboxes ED-038 is an Ethernet to Digital I/O Relay device with 3 digital input lines and 3 Form A (SPST, normally open) relay outputs, plus one RJ45 Ethernet port. The datasheet gives connector pin outs for the power terminal, Ethernet port and 10-way terminal block, together with the electrical and environmental specifications of the unit.
Configuration and monitoring are done from a web page, so no software is required, and the device supports Modbus TCP or ASCII commands. It is powered from an unregulated +5 V to +30 V DC supply, has 1500 V RMS magnetic isolation from Ethernet, and comes in an IP-30 rated non-conducting polyamide case rated for 0 ºC to +60 ºC operation.
| Digital inputs | 3 digital input lines (NPN/PNP) |
|---|---|
| Relay outputs | 3 Form A (SPST), normally open |
| Power supply input | +5 V to +30 V DC, unregulated, reverse polarity protection |
| Power consumption | 2.5 W max; 220 mA @ +5 V DC / 36 mA @ +30 V DC |
| Isolation | 1500 V RMS magnetic isolation from Ethernet |
| Relay contact rating | 5 A @ 30 VDC, 5 A @ 250 VAC, 5 A @ 110 VAC |
| Relay on/off time | 10 ms max |
| Expected relay life | 100,000 operations (typical) |
| Initial contact resistance | 30 milliohms max |
| Ethernet port | RJ45, 10/100 autosensing, Auto MDIX |
| Operating temperature | 0 ºC to +60 ºC / +32 ºF to +140 ºF |
| Storage temperature | 0 ºC to +70 ºC / +32 ºF to +158 ºF |
| Relative humidity | 5 to 95% non-condensing |
| Housing | IP-30 rated non-conducting polyamide case |
| Packaged weight | 0.230 kg / 8.11 ounces |
| GTIN | 837324009835 |
Logic level 0 is -30 V to +1 V and logic level 1 is +2 V to +30 V. The pull-up or pull-down for NPN or PNP sensors is individually jumper selectable.
The relays are normally open and stay open when power is removed from the ED-038.
No. Configuration, monitoring and control are done from the device's web page, so no software is required.
Yes, the device works as a Modbus TCP server, and Modbus TCP can be used on the input and output lines.
No, there is no serial port on this device; the datasheet refers to the ED-004 or ED-204 instead.