Product manual for Advanced Mx-5100, Mx-5200, Mx-5400 and Mx-5800 fire alarm panels covering installation, wiring, programming, service and maintenance.
This manual covers the Advanced Mx-5100, Mx-5200, Mx-5400 and Mx-5800 fire alarm panels and is applicable from software version 5000-050-04 onwards. It describes installation, wiring, programming, service and maintenance, and states that the panels conform to EN54-2 and EN54-4.
The contents include identification of parts, loop driver and peripheral module installation, wiring installation, programming menus, maintenance schedules, component replacement and appendices.
| Part Number | Mx-5100, Mx-5200, Mx-5400, Mx-5800 |
|---|---|
| Enclosure | Steel IP30 RAL7035 |
| Temperature | -5 C to 40 C |
| Humidity | 95% RH max |
| AC Supply | 200-240V +10%, -15%, 47-63 Hz AC |
| Battery Capacity | 24V 4Ah internal (min) |
| Power Supply | On-board 24V DC, 3A or 5A |
| Output Voltage | 18.0V to 28.0V |
| Ripple | 1.0V pk-pk |
| Max Battery Ohms | 1.6 ohm +/- 0.1 ohm |
| Fire Zones | 200 max per panel (2000 when networked) |
| Loops | 1 to 8 |
| Loop Current | 500mA max per loop |
| Devices per Loop | Apollo 126 detector/call points per loop (max) |
| Protocols | Apollo S90, XP95, Discovery, Explorer and Hochiki ESP |
| Sounder Outputs | 2 x 1A programmable |
| Relay Outputs | 2 x 1A 30V AC/DC (max) |
| Auxiliary Output | 24V DC, 500mA |
| Display | LCD white backlit 240 x 64 graphical |
| Programmable Inputs | 8x switch inputs, 1 hard wired input and four programmable push buttons |
| Interfaces | USB B type interface and RS232 |
| Network | Optional |
| Event Log | 5000 event and diagnostic plus 500 fire |
The functions are available from software version 5000-050-04 onwards.
The operating temperature range is -5 C to 40 C.
The maximum humidity rating is 95% RH.
The event log stores 5000 events and diagnostics plus 500 fire events.