The ifm PP755X operating instructions describe a pressure sensor that monitors system pressure in a plant and is suited for use in mobile vehicles. The document covers safety instructions, functions and features, application area, communication and parameter setting, operating modes, pressure monitoring and switching functions, and the teach function.
It also provides installation and electrical connection instructions, parameter setting details including adjustable parameters and menu structure in PP2001, operation indications, fault indication, a scale drawing, technical data and factory settings.
| Type of pressure | Relative pressure |
|---|---|
| Process connection | G¼ |
| Recommended tightening torque | 25 Nm (max. 50 Nm) |
| Output | PNP transistor output |
| Communication | IO-Link |
The unit monitors the system pressure in a plant, and the document states that it is suited for use in mobile vehicles.
The unit provides process data via IO-Link and supports bidirectional communication with the ifm PP2001 handheld programming unit or a PC/controller via IO-Link.
Before installing or removing the unit, make sure no pressure is applied to the system, insert the unit in a G¼ process connection, and tighten firmly; the recommended tightening torque is 25 Nm.