Dell MRVDY 913CC 6WWDY UPS Power Cord Installation Instructions

This document describes the installation instructions for Dell UPS power supplies.


Dell MRVDY 913CC 6WWDY UPS Power Cord Installation Instructions - cover page
Brand
DELL
Category
power system
Document type
Installation Guide
Language
English
Pages
2
File format
PDF
File size
855 KB
Published
25 November, 2023
Updated
25 November, 2023
Models
913CC, 6WWDY
MD5 checksum
A1DE82682FE1195D14F35D18105FCAB6

About this manual

This two-page Dell document gives the instructions for installing an optional power cord on selected Dell UPS models. It opens with a warning that electrical installation must be carried out only by qualified service personnel such as a licensed electrician, that utility power must be switched off at the distribution point where the UPS will be connected, and that the UPS user's manual should be consulted for more information. The same warning and notes are repeated in several languages.

The second part lists which power cord goes with which UPS model: MRVDY for 4200W 208 Vac UPS, 913CC for 3750W, 4200W or 5600W 230 Vac UPS, and 6WWDY for 4200W or 5600W 230 Vac UPS, with a note that the cord is not for use with the 5600W Online UPS. A table then gives the terminal positions (G for input ground, N for L2/Neutral in, L for L1/Line in), the wire size rating of 5.26–16 mm2 (10–6 AWG) and a tightening torque of 2.26 Nm (20 lb in), followed by the copyright and trademark notice dated October 2011.

What's inside

  • Electrical installation warning
  • Optional power cord models
  • Power Cord Installation
  • Wire function and terminal position
  • Wire size rating
  • Tightening torque
  • Trademarks and copyright

Specifications

Wire size rating5.26–16 mm2 (10–6 AWG)
Terminal tightening torque2.26 Nm (20 lb in)
Terminal positionsG = input ground, N = L2/Neutral in, L = L1/Line in
Power cord for MRVDY4200W, 208 Vac UPS
Power cord for 913CC3750W, 4200W, or 5600W, 230 Vac UPS
Power cord for 6WWDY4200W or 5600W, 230 Vac UPS

Frequently asked questions

Which Dell UPS models accept the optional power cord?

MRVDY on the 4200W 208 Vac UPS, 913CC on the 3750W, 4200W or 5600W 230 Vac UPS, and 6WWDY on the 4200W or 5600W 230 Vac UPS.

What wire size is rated for the input terminals?

The terminal wire size rating is 5.26–16 mm2 (10–6 AWG).

What tightening torque should be used on the terminals?

The tightening torque is 2.26 Nm (20 lb in).

Can the power cord be used with the 5600W Online UPS?

No, the document states the cord is not for use with the 5600W Online UPS.

Download PDF (855 KB)