This manual provides a guide to the operation of the controllers mounted on Trane RTAD chillers.
This owner manual guides operation of the UCM-CLD controller mounted on Trane RTAD chillers. It describes the eight-module control system, operator interface, menus, setpoints, diagnostics and safety recommendations.
The manual also covers warnings and cautions, reception and warranty conditions, maintenance contract recommendations, and password-protected service settings and tests reserved for Trane Service Engineers.
| Control modules | Eight electronic modules, each with its own 115V or 24V power supply |
|---|---|
| Display | 2-line, 40-character liquid-crystal display |
| Keyboard | 16-key touchpad |
| Remote CLD distance | Up to 1500 m from the unit |
| Remote CLD communication | Up to four units of the same type |
| Panel ice termination setpoint range | -6.6 to -0.5 C |
| Low ambient lockout setpoint range | -28.8 to 15.5 C |
| Front panel current limit setpoint range | 40% to 120% |
| Chilled water pump off delay range | 1 to 30 min |
The chiller performs an Emergency Stop and does not unload.
It is composed of eight electronic modules, each with its own 115V or 24V power supply.
Levels 2 and 3 are reserved for Trane Service Engineers.
Repair or modification without written approval, exceeding operating limits, or modifying the control system or wiring can void the warranty.