Dell Tower UPS 500W, 1000W and 1920/1500W User's Guide H900N, J715N, K788N, H914N, J716N, K789N K806N, H965N
This user's guide covers the Dell Tower UPS 500W, 1000W, and 1920/1500W models and describes installation, startup and shutdown, control panel functions, additional features, maintenance, specifications, and troubleshooting.
The UPS protects connected equipment from power failures, power sags, power surges, brownouts, and line noise. Features include buck and boost voltage regulation, start-on-battery capability, battery replacement without powering down the UPS, optional external battery module support on 1000W and 1920/1500W models, USB and DB-9 serial ports, and an optional network management card.
| UPS model variants | 500T LV (H900N), 500W; 1000T LV (K788N), 1000W; 1920T LV (J716N), 1920W (1500W at 100V); 500T HV (J715N), 500W; 1000T HV (H914N), 1000W; 1920T HV (K789N), 1920W |
|---|---|
| External battery module models | 1000T EBM (K806N), 36 Vdc; 1920T EBM (H965N), 72 Vdc |
| Weight, 500W UPS | 11.6 kg (25.6 lb) |
| Weight, 1000W UPS | 18.3 kg (40.3 lb) |
| Weight, 1920/1500W UPS | 30.5 kg (67.2 lb) |
| Weight, 1000W EBM | 23.1 kg (47.6 lb) |
| Weight, 1920W EBM | 42.5 kg (93.6 lb) |
| Maximum ambient temperature | 40 °C (104 °F) |
| Maximum humidity | 95% |
| Communication ports | USB and DB-9 serial port |
| External battery module support | 1000W and 1920/1500W models support a maximum of one EBM |
| Branch circuit overcurrent protection, 500W | 15A at 120V and 230V |
It protects connected equipment from power failures, power sags, power surges, brownouts, and line noise.
Yes, the design allows safe replacement of batteries without powering down the UPS.
Yes, it has start-on-battery capability for powering up even if utility power is not available.
The 1000W and 1920/1500W models can be connected to a maximum of one external battery module.