The PR standard is an easy-to-implement field test standard.
This document is an installation guide for PR electronics 3000 series 6 mm temperature transmitters. It covers safety, installation, power supply options, wiring, technical parameters, connections, LED indicators, DIP switch configuration and temperature range settings.
The covered models are 3101, 3102, 3111, 3112, 3113, 3331, 3333 and 3337. It includes installation on DIN rail or power rail, flexible power supply arrangements, and Zone 2/Division 2 certification information. This manual is written in Chinese.
| Wire size | AWG 26-12 / 0.13 x 2.5 mm2 |
|---|---|
| Screw terminal torque | 0.5 Nm |
| Fuse rating (PR 9410 power rail) | 0.4 A |
| Fuse rating (DIN rail daisy chain) | 2.5 A |
| Power supply (DIN rail daisy chain) | 24 VDC ±30% |
| Power rail terminal current | Maximum 400 mA |
| Altitude | At least 2000 m |
| Enclosure rating for Zone 2 | At least IP54 |
| TC J range | -100 to +1200 °C |
| TC K range | -180 to +1372 °C |
| Pt100 range | -200 to +850 °C |
| Measurement category and pollution degree | Measurement category II, pollution degree 2 |
Models 3101 and 3111 support TC inputs only.
Models 3102, 3112 and 3333 support Pt100 inputs only.
Power must be restarted.
Wire sizes from AWG 26 to AWG 12 are supported.