This product complies with the following standards: CE-marked for Low Voltage Directive. IEC 664-1 Insulation Coordination within Low Voltage Systems. UL 840 Insulation Coordination for electrical equipment. EN50081-2 EMC Generic Emissions Standard, Industrial Level. EN50082-2 EMC Generic Immunity Standard, Industrial Level. Enclosure ingress protection, EN60529 IP00, NEMA 250. Flammability rating according to UL 94.
This document is the User Guide for the Optidrive PI Control Option module, designed for professional incorporation into complete equipment or systems. It details the safety precautions, installation requirements, and standards conformity for the module when used with Optidrive variable speed drives.
The guide provides technical specifications for the module's inputs and outputs, including rated reference and feedback inputs, gain ranges, and environmental limits. It also explains the operational modes, switch settings for mode selection, and procedures for adjusting potentiometers for proportional gain and reference voltage presets.
| Rated reference input | +/- 10V DC or 4…20mA |
|---|---|
| Rated feedback input | +/- 10V DC or 4…20mA |
| Proportional gain range | 0.2 …. 30 |
| Integral gain settings | 0.1s, 1s, 10s |
| Max input voltage | +/- 50V DC |
| Environmental temperature range | -10ºC … +50ºC |
| Ingress protection | IP00 |
The rated reference input is +/- 10V DC or 4…20mA, and the rated feedback input is also +/- 10V DC or 4…20mA.
The proportional gain range is from 0.2 to 30.
The available integral gain settings are 0.1s, 1s, and 10s.
The maximum input voltage is +/- 50V DC.