Invertek Drives Optidrive Eco AC Variable Speed Drive Advanced User Guide

This document is an instruction manual for Optidrive Eco variable speed drive.


Invertek Drives Optidrive Eco AC Variable Speed Drive Advanced User Guide - cover page
Brand
Invertek Drives
Category
inverter
Document type
User Manual
Language
English
Pages
33
File format
PDF
File size
1.5 MB
Published
26 October, 2023
Updated
26 October, 2023
MD5 checksum
3EEE5B7873835DE6B9C01810AB9100DB

About this manual

This Advanced User Guide from Invertek Drives describes the parameter set of the Optidrive Eco AC variable speed drive, rated 0.75 kW – 250 kW / 1 HP – 350 HP at 200 – 480 Volt, 1 and 3 phase. It is written for persons already familiar with the installation, mounting, start-up and operation of the equipment, and is meant to be read together with the Optidrive Eco User Guide supplied with each product, including all safety information and warnings. The document applies to version 2.10 firmware.

The guide explains the parameter structure across Groups 0 to 9, with access levels and access codes set through P1-14, and gives descriptions of parameters such as maximum and minimum frequency, ramp times, stop mode, motor rated voltage, current, frequency and speed, torque boost and command source. It also covers Programmable Logic functions (Group 9), monitoring parameters (Group 0), P6-28 value selection, diagnostic and fault messages, immunity tests (ESD, EFT/B, surge, dielectric strength) and general technical and performance data.

What's inside

  • Optidrive Eco Parameter Set Overview
  • Parameter Structure Overview
  • Parameter Descriptions
  • Parameter Group 9 – Programmable Logic Functions
  • Parameter Group 0 – Monitoring Parameters (Read Only)
  • P6-28 Value Selection
  • Diagnostic and Fault Messages
  • Immunity Tests
  • General Technical and Performance Data

Specifications

Drive power range0.75kW – 250kW / 1HP – 350HP
Supply voltage200 – 480 Volt, 1 & 3 Phase
Firmware version2.10
Default motor rated frequency (kW models)50 Hz
Default motor rated frequency (HP models)60 Hz
Default motor rated voltage, 200–240 V models230 Volts, maximum 250 Volts
Default motor rated voltage, 380–480 V models400 Volts, maximum 500 Volts
Acceleration ramp time range0.0 to 6000 seconds, default 30

Frequently asked questions

What is the factory setting of the extended parameter access code P1-14?

P1-14 set to P2-40 (factory setting 101) allows extended parameter access; setting P1-14 = P6-30 (factory setting 201) allows advanced parameter access.

Which firmware version does this Optidrive Eco guide apply to?

The document is for use with version 2.10 firmware.

What stop modes can be selected with P1-05?

0: Ramp to stop, 1: Coast to stop, and 2: AC Flux Braking.

What current should be entered in P1-08?

P1-08 should be set to the rated (nameplate) current of the motor; the factory default is the maximum continuously available output current of the drive.

Download PDF (1.5 MB)

More Invertek Drives Manuals


View all Invertek Drives manuals →