This document describes the safety precautions for NE-S1 series inverters, including installation and wiring.
Safety precautions for the Hitachi NE-S1 series inverter are classified as WARNING or CAUTION. The document says the Instruction Manual and appended documents must be read thoroughly before installation or operation, and the QRG should be read before maintenance and service. It is intended for each product and should be delivered to the end user of the inverter.
The precautions cover installation, wiring, operation, maintenance, inspection and parts replacement, and other items. A section on UL and cUL cautions lists conditions such as a 50 ºC maximum surrounding air temperature, 60/75ºC CU wire, tightening torque and wire ranges for NES1 models, fuse/circuit breaker ratings, and includes a wiring diagram of inverter.
| Maximum surrounding air temperature rating | 50 ºC |
|---|---|
| Motor overload protection trip level | max. 150 % of FLA |
| Suitable supply circuit | not more than 100,000 rms symmetrical amperes, 240 V maximum |
| Required wire type | 60/75ºC CU wire only |
| NES1-007S tightening torque and wire range | 1.8 N.m; 14~12 AWG |
The Instruction Manual and appended documents must be read thoroughly before installing or operating the inverter.
Turn off the power supply and wait at least 10 minutes, and confirm that the Charge lamp is off before inspection.
Use 60/75ºC CU wire only.
The required torque is 1.8 N.m for a wire range of 14~12 AWG.