The LHQ-Y-001 V2.0 is a high-performance electrochemical hydrogen sulfide gas sensor probe that measures the concentration of hydrogen sulfide in the air by reacting hydrogen sulfide with oxygen at the working electrode. It has a high sensitivity to hydrogen sulfide over a wide range of concentrations.
The Firstrate LHQ-Y-001 V2.0 is an electrochemical hydrogen sulfide gas sensor designed for industrial environments. It measures H₂S concentrations from 0 to 100 ppm with 0.1 ppm resolution and ±(0.5 ppm + 2% FS) accuracy. The device operates on 12–24 V DC, consumes less than 200 mA, and communicates via RS‑485 using Modbus RTU protocol at a default baud rate of 9600. It features surge‑protected 485 interfaces, a warm‑up time under 30 minutes, response time under 10 seconds, and a service life exceeding five years.
The manual provides wiring instructions (red: power+, black: common, green: RS485A, white: RS485B), detailed Modbus register maps for real‑time data (concentration, temperature, status) and configuration parameters (ID, baud rate, alarm thresholds), and precautions for installation and maintenance. The manufacturer, Hunan Firstrate Sensor Co., Ltd., offers a one‑year warranty and lifetime repair service. This manual is written in Chinese.
| Measurement range | 0-100 ppm |
|---|---|
| Resolution | 0.1 ppm |
| Measurement accuracy | ±(0.5 ppm + 2% FS) |
| Supply voltage | DC 12V-24V |
| Current consumption | <200 mA |
| Warm-up time | <30 minutes |
| Response time | <10 seconds |
| Operating temperature | -10°C to 50°C |
| Operating humidity | 0-95% RH non-condensing |
| Weight | <200 g |
| Installation method | Wall-mounted |
| Service life | >5 years |
| Default baud rate | 9600 |
| Data bits | 8 |
| Stop bits | 1 |
The measurement range is 0 to 100 ppm.
The default baud rate is 9600.
The sensor has four wires: red for power positive, black for common, green for RS485A, and white for RS485B.
The operating temperature range is -10°C to 50°C.