Chenzhu CZSR8401-1A Safety Relay User Manual

The CZSR8401-1A is a safety relay control module that receives safety switch signals from the field and implements safe and reliable isolation control of high-voltage circuits. It supports single-channel operation, and its internal circuit adopts Fail-safe technology, triple redundancy technology and contact fusion protection technology, which meets the requirements of IEC61508 and has a functional integrity level of up to SIL3.


Chenzhu CZSR8401-1A Safety Relay User Manual - cover page
Brand
Chenzhu
Category
electric relay
Document type
User Manual
Language
Chinese
Pages
2
File format
PDF
File size
551 KB
Published
15 November, 2023
Updated
15 November, 2023
MD5 checksum
E3F59407EFEF411D1CFA56262768005A

About this manual

This document is the Chinese user manual (使用说明书) for the CZSR8401-1A safety relay from Chenzhu (辰竹). The CZSR8401-1A is a safety relay control module that receives signals from field safety switches and provides safe, isolated control of high-voltage circuits. It supports single-channel operation and uses fail-safe circuitry, triple redundancy and contact-welding protection, meeting the IEC 61508 standard with a safety integrity level of up to SIL3.

The manual covers wiring and installation on a DIN 35mm rail inside a control cabinet with at least IP54 protection, removal from the rail, and periodic maintenance checks. It also lists the main technical parameters (power supply, input, output and timing characteristics), safety certification data, dimensions, a function block diagram and typical applications. Contact details for Chenzhu's sales and technical support hotline (400 881 0780) are included. This manual is written in Chinese.

What's inside

  • 概述 (Overview)
  • 接线 (Wiring)
  • 安装 (Installation)
  • 拆卸 (Removal)
  • 维护 (Maintenance)
  • 主要技术参数 (Main Technical Parameters)
  • 安全认证 (Safety Certification)
  • 典型应用 (Typical Applications)
  • 外形尺寸 (Dimensions)
  • 功能框图 (Function Block Diagram)

Specifications

Current consumption≤60mA (24V DC)
Input current≤60mA (24V DC)
Input devicesSafety switches, contact switches
Contact configuration1NO
Contact capacity2A/230V AC; 2A/40V DC
Contact fuse protection2.5A internal fuse
Response/release time≤10ms; recovery time ≤100ms
Safety integrity levelSIL3 per IEC 61508
PFHd2.03E-10/h
Dimensions (D×H×W)114.5mm × 99.0mm × 22.5mm
Operating temperature-20℃ to +60℃
Protection degreeIP20
Insulation strength1500V AC, 1min
EMCEN60947, EN61000-6-2, EN61000-6-4

Frequently asked questions

What power supply does the CZSR8401-1A use?

The relay is powered by a 24V DC supply (16–35V DC range); using 220V AC is strictly prohibited.

Where should the safety relay be installed?

It must be installed in a control cabinet with at least IP54 protection, mounted on a DIN 35mm rail.

What safety level does the CZSR8401-1A meet?

It complies with IEC 61508 and reaches safety integrity level SIL3, with an HFT of 1 and SFF of 99%.

What is the warranty period?

Chenzhu provides free repair for quality problems occurring within five years of shipment under normal use.

Download PDF (551 KB)

More Chenzhu Manuals


View all Chenzhu manuals →