The CZSR8401-1A is a safety relay control module that receives safety switch signals from the field and implements safe and reliable isolation control of high-voltage circuits. It supports single-channel operation, and its internal circuit adopts Fail-safe technology, triple redundancy technology and contact fusion protection technology, which meets the requirements of IEC61508 and has a functional integrity level of up to SIL3.
This document is the Chinese user manual (使用说明书) for the CZSR8401-1A safety relay from Chenzhu (辰竹). The CZSR8401-1A is a safety relay control module that receives signals from field safety switches and provides safe, isolated control of high-voltage circuits. It supports single-channel operation and uses fail-safe circuitry, triple redundancy and contact-welding protection, meeting the IEC 61508 standard with a safety integrity level of up to SIL3.
The manual covers wiring and installation on a DIN 35mm rail inside a control cabinet with at least IP54 protection, removal from the rail, and periodic maintenance checks. It also lists the main technical parameters (power supply, input, output and timing characteristics), safety certification data, dimensions, a function block diagram and typical applications. Contact details for Chenzhu's sales and technical support hotline (400 881 0780) are included. This manual is written in Chinese.
| Current consumption | ≤60mA (24V DC) |
|---|---|
| Input current | ≤60mA (24V DC) |
| Input devices | Safety switches, contact switches |
| Contact configuration | 1NO |
| Contact capacity | 2A/230V AC; 2A/40V DC |
| Contact fuse protection | 2.5A internal fuse |
| Response/release time | ≤10ms; recovery time ≤100ms |
| Safety integrity level | SIL3 per IEC 61508 |
| PFHd | 2.03E-10/h |
| Dimensions (D×H×W) | 114.5mm × 99.0mm × 22.5mm |
| Operating temperature | -20℃ to +60℃ |
| Protection degree | IP20 |
| Insulation strength | 1500V AC, 1min |
| EMC | EN60947, EN61000-6-2, EN61000-6-4 |
The relay is powered by a 24V DC supply (16–35V DC range); using 220V AC is strictly prohibited.
It must be installed in a control cabinet with at least IP54 protection, mounted on a DIN 35mm rail.
It complies with IEC 61508 and reaches safety integrity level SIL3, with an HFT of 1 and SFF of 99%.
Chenzhu provides free repair for quality problems occurring within five years of shipment under normal use.