This manual covers the operation, installation, and maintenance of the Chenzhu GS8272-EX.AMR isolated safety barrier for thermocouple and RTD inputs.
The Chenzhu GS8272-EX.AMR is a single-channel isolated safety barrier designed for thermocouple and thermoresistance (RTD) inputs. It converts temperature signals into 4-20mA signals, isolating them from the hazardous side to the safe side. The device also provides an RS485 bus output based on the MODBUS-RTU protocol and two relay alarm outputs. Power and RS485 communication can be connected via a rail, while current and relay outputs require terminal block connections. The unit requires independent power supply with isolation between power, input, and output. This manual is written in Chinese.
| Supply Voltage | 20~35V DC |
|---|---|
| Output Current Range | 4~20mA |
| Load Resistance | ≤300Ω |
| Response Time | ≤1.5s |
| Conversion Accuracy | 0.1%F.S. |
| Operating Temperature | -20℃~+60℃ |
| Weight | About 150g |
| Dimensions | 118.9mm×106.0mm×17.5mm |
The device supports T, E, J, K, N, R, S, and B type thermocouples.
The device supports Pt100, Cu50, and Cu100 thermoresistors.
The RS485 output uses the MODBUS-RTU protocol.
No, it must be powered by 24V DC; using 220V AC is strictly prohibited.