The document describes the features and specifications of the VECTRON L series of oil-fired boilers.
This document covers the ELCO VECTRON L series of light-oil burners in three sizes: VECTRON L 02.120, 02.160 and 02.210 (also written VL02.120, VL02.160, VL02.210). It is a bilingual Russian/Spanish document dated 05/2009 (Art. Nr. 4200 1018 6700A) containing technical specifications, burner power curves, electrical and hydraulic schematics, and spare parts lists.
The specifications cover burner output (80–120, 110–160 and 140–210 kW), fuel consumption, electrical data, the SH 113 control and safety box, the MZ 770 S flame monitor, the EBI-M ignition device and the AS 47D atomizing pump. The spare parts section lists part numbers for components such as the nozzle line, fan wheel, motor, pump and DANFOSS nozzles for each model. The document states it was produced in the EU and is non-contractual. This manual is written in Russian.
| Emission class | Class 2 per EN 267 |
|---|---|
| Fuel consumption min./max. | 6.7-10.1 / 9.3-13.5 / 11.8-17.7 kg/h |
| Fuel type | Extra-light fuel oil (Gasóleo EL) per each country's standards |
| Mains voltage | 230V - 50Hz |
| Electrical power absorbed (in operation) | 205W / 270W / 290W |
| Approximate weight | 18 kg |
| Motor | 160W; 2850 min-1 (02.120/160), 130W; 2900 min-1 (02.210) |
| Degree of protection | IP 21 |
| Control and safety box | SH 113 |
| Flame monitor | MZ 770 S |
| Ignition device | EBI-M 2 x 7.5 kV |
| Atomizing pump | AS 47D - 58 ltr./h |
| Noise level (VDI 2715) | 62 / 64 / 65 dB(A) |
| Max. ambient temperature | 60°C |
| Suction line | 4 x 6 mm |
They run on extra-light fuel oil (Gasóleo EL) that meets the standards of each country.
A 230V - 50Hz supply; power absorbed in operation is 205W, 270W or 290W depending on the model.
The SH 113 control and safety box, with an MZ 770 S flame monitor and an EBI-M 2 x 7.5 kV ignition device.
The burner output QF equals the boiler nominal output QN divided by the boiler efficiency ηK.