Red Lion PM50AO-A Analog Output Module Installation Guide

The PM50AO-A is an analog output module with the following features: - 1 analog output channel - Output range: 0-10V, 0-20mA, 4-20mA - Resolution: 12-bit - Accuracy: 0.1% - Response time: <10ms - Isolation: 1500Vrms


Red Lion PM50AO-A Analog Output Module Installation Guide - cover page
Brand
Redlion
Category
Automation control Equipment
Document type
Installation Guide
Language
English
Pages
4
File format
PDF
File size
985 KB
Published
09 November, 2023
Updated
09 November, 2023
MD5 checksum
EB4590DB1AEE398A3D38E3437A46C4BE

About this manual

This installation guide for the Red Lion PM50AO-A analog output module covers the module package checklist, dimensions, safety summary, ordering information, and specifications. It describes hardware installation on 4.3 inch and 3.5 inch PM-50 hosts, module removal, wiring connections, and LED states, and it ends with technical support and limited warranty information.

The PM50AO-A provides a retransmitted analog output of 0 (4) to 20 mA or 0 to 10 VDC, ±10 VDC and uses a removable terminal block. The guide lists a maximum power of 1.3 W, an operating temperature range of -10 to 55 °C, and an IP25 plastic enclosure. It also notes that a 4.3 inch PM-50 host accepts up to 5 modules, a 3.5 inch host accepts up to 3, and only one module from each function type can be installed.

What's inside

  • Module Package Checklist
  • Dimensions
  • Safety Summary
  • Ordering Information
  • Specifications
  • Hardware Installation
  • Wiring Connections
  • LEDs
  • Technical Support
  • Limited Warranty

Specifications

Output Types0 to 10 V, ±10 V, 0 to 20 mA, or 4 to 20 mA
Maximum Power1.3 W
Isolation to Sensor & User Input Commons500 Vrms
Effective ResolutionFull 16-bit (Signed)
Operating Temperature Range-10 to 55 °C
Storage Temperature Range-40 to 85 °C
Weight1.8 oz (51.1 g)
Enclosure RatingIP25
Voltage Output Minimum Load500 ohm min. (20 mA max.)
Current Output Compliance500 ohm max. (10 V max.)

Frequently asked questions

What output types does the PM50AO-A support?

It supports 0 to 10 V, ±10 V, 0 to 20 mA, or 4 to 20 mA outputs.

What is the maximum power consumption of the PM50AO-A?

The maximum power is 1.3 W.

How many PM-50 modules can a 4.3 inch host accept?

A 4.3 inch host accepts a maximum of 5 modules; a 3.5 inch host accepts a maximum of 3.

What is the operating temperature range of the PM50AO-A?

The operating temperature range is -10 to 55 °C.