The TU7685 is a microprocessor-based sludge concentration (SS) controller that uses an infrared light scattering measurement method. The sensor light source uses an LED diode to emit light, which has the advantages of accurate measurement, stable performance and long service life.
This installation and operation manual covers the B&C TU7685 sludge concentration (SS) monitor together with the TU8182 immersion sensor. The document is published by Shanghai Anbi Environmental Protection Equipment Co., Ltd. (www.absh.cn). It describes the measuring principle, the measuring ranges, the panel-mount dimensions, the sensor installation, the terminal wiring, and the configuration settings that are made with the MODE, CAL, ENT and arrow keys.
The TU7685 is a microprocessor-based instrument that uses an infrared light scattering method; the sensor light source is an LED diode. It offers two banks and four ranges (0-9, 0-999, 0-99 and 0-9999 mg/l) selectable in units of NTU, mg/l or ppm, a 0-20 mA or 4-20 mA analog output, two SPDT control relays, an SPST alarm relay and an SPST cleaning relay. The manual walks through the configuration menu step by step and explains the main displays and the AUTO/MAN operating modes. This manual is written in Chinese.
| Measuring principle | Infrared light scattering method with LED light source |
|---|---|
| Measuring ranges | Two banks, four ranges: 0-9, 0-999, 0-99 and 0-9999 mg/l |
| Measuring units | NTU, mg/l, ppm |
| Power supply | 220 V / 50 Hz |
| Monitor dimensions | 96 × 96 × 155 mm |
| Panel cutout | 91.5 × 91.5 mm |
| Analog output | 0-20 mA or 4-20 mA |
| Response time, large signal change | 5-220 s, factory setting 40 s |
| Control relays | Two SPDT control relays |
| Sensor cable | 7.5 m, 7-core cable supplied with the TU8182 sensor |
It uses an infrared light scattering method; the sensor contains an LED infrared light source, a light signal detector, a lens condition detector and a preamplifier.
There are two banks with four ranges: 0-9 and 0-999 mg/l, or 0-99 and 0-9999 mg/l, with units selectable as NTU, mg/l or ppm.
The monitor is powered from 220 V / 50 Hz through the numbered terminals on the back (1 neutral, 3 live, 4 ground).
Its 7-core cable is wired to the matching terminal numbers on the back of the TU7685; if the cable must be extended, a highly insulated junction box should be used rather than cutting the cable.