Ultima® OPIR-5 Infrared Open Path Gas Detector Safety Manual
This safety manual from MSA describes safety-related information for installing, using, configuring and maintaining the Ultima OPIR-5 Infrared Open Path Gas Detector. It states that the detector continuously monitors hydrocarbon gases and provides a 4-20 mA analog signal proportional to LEL gas concentration, with an optional LEL relay output. A heavy hydrocarbon (propane) version monitors gases in the 0 to 1 LEL·m range.
The manual covers installation and location considerations, operation and maintenance, environmental and electrical specifications, and certifications and failure-rate data. It notes that the Ultima OPIR-5 is a Type B field device according to IEC 61508, and that its safety function does not include HART or Modbus RS-485 communication. This manual is written in Portuguese.
| Operating temperature range | -55°C to 65°C (-67°F to 149°F) |
|---|---|
| Humidity range | 10 to 95% RH, non-condensing |
| Input voltage | 20 to 36 VDC |
| Transmitter power supply with heater | 12 W |
| Receiver power supply with relays and heater | 10 W |
| Standard unit range and output | 0 to 5 LEL·m, 4 to 20 mA |
| Heavy hydrocarbon unit range and output | 0 to 1 LEL·m, 4 to 20 mA |
| Analog output maximum load | 600 ohms |
| Response time T90 | ≤ 10 seconds |
| Product lifetime | 10 to 12 years |
It continuously monitors hydrocarbon gases and transmits a 4-20 mA analog signal proportional to LEL gas concentration, with an optional LEL relay output.
The standard unit range is 0 to 5 LEL·m with a 4 to 20 mA output.
It performs internal diagnostics of critical faults every second.
No. The manual states that the detector does not respond to gas leaks if the IR beam is fully blocked.