MSA Ultima OPIR-5 Infrared Open Path Gas Detector Safety Manual

Ultima® OPIR-5 Infrared Open Path Gas Detector Safety Manual


MSA Ultima OPIR-5 Infrared Open Path Gas Detector Safety Manual - cover page
Brand
MS­A
Category
detectors
Document type
Other
Language
Portuguese
Pages
8
File format
PDF
File size
211 KB
Published
06 November, 2023
Updated
06 November, 2023
MD5 checksum
93EA0E0B1BE43E9C2AC6AFC86A024975

About this manual

This safety manual from MSA describes safety-related information for installing, using, configuring and maintaining the Ultima OPIR-5 Infrared Open Path Gas Detector. It states that the detector continuously monitors hydrocarbon gases and provides a 4-20 mA analog signal proportional to LEL gas concentration, with an optional LEL relay output. A heavy hydrocarbon (propane) version monitors gases in the 0 to 1 LEL·m range.

The manual covers installation and location considerations, operation and maintenance, environmental and electrical specifications, and certifications and failure-rate data. It notes that the Ultima OPIR-5 is a Type B field device according to IEC 61508, and that its safety function does not include HART or Modbus RS-485 communication. This manual is written in Portuguese.

What's inside

  • Introduction
  • General description
  • Installation
  • Location considerations
  • Operation and maintenance
  • Specifications
  • Certifications and failure rate data

Specifications

Operating temperature range-55°C to 65°C (-67°F to 149°F)
Humidity range10 to 95% RH, non-condensing
Input voltage20 to 36 VDC
Transmitter power supply with heater12 W
Receiver power supply with relays and heater10 W
Standard unit range and output0 to 5 LEL·m, 4 to 20 mA
Heavy hydrocarbon unit range and output0 to 1 LEL·m, 4 to 20 mA
Analog output maximum load600 ohms
Response time T90≤ 10 seconds
Product lifetime10 to 12 years

Frequently asked questions

What does the MSA Ultima OPIR-5 monitor?

It continuously monitors hydrocarbon gases and transmits a 4-20 mA analog signal proportional to LEL gas concentration, with an optional LEL relay output.

What is the standard Ultima OPIR-5 detection range?

The standard unit range is 0 to 5 LEL·m with a 4 to 20 mA output.

How often does the detector perform internal diagnostics?

It performs internal diagnostics of critical faults every second.

Does the Ultima OPIR-5 respond if the IR beam is fully blocked?

No. The manual states that the detector does not respond to gas leaks if the IR beam is fully blocked.