This manual describes how to use the NTC Room Controller, including the controller's appearance and display, general information, installation site selection, installation steps, electrical connections, controller configuration, troubleshooting and other contents.
The Carrier CRC2 NTC Room Controller 2 is a room controller for hydronic fancoil units. This control system operates only with all hydronic indoor units, and the Room Controller 2 requires 12 VDC from the connected unit; it requires no batteries and is not “power stealing.”
The installation manual covers the display and keys, choosing the installation site, mounting, electrical connections, configuration menu, and troubleshooting. It states a maximum of 150 m total network wiring and recommends BELDEN 9842 or a 4x0.5mm2 multiple double insulated cable for distances longer than 3 m.
| Power supply | 12 VDC from the connected unit |
|---|---|
| Maximum total network wiring | 150 m |
| Recommended cable for distances longer than 3 m | BELDEN 9842 or 4x0.5mm2 multiple double insulated cable (H03VV-F) |
| Recommended mounting height | Approximately 1.5 m from floor |
It requires 12 VDC to be connected for proper operation, supplied from the connected unit.
Keep the MODE button pressed for at least 5 seconds; “1-” is displayed on the screen.
The maximum is 150 m of total network wiring.
Mis-wiring of the 12 V power to the Room Controller 2 control is listed as a possible cause.