Carrier TEMP System Unitary Controller Thermostat Installation, Service, and Troubleshooting Instructions

This manual provides installation, configuration, troubleshooting, and operational instructions for the Carrier TEMP System Unitary Controller Thermostat…


Carrier TEMP System Unitary Controller Thermostat Installation, Service, and Troubleshooting Instructions - cover page
Brand
Carrier
Category
Other
Document type
User Manual
Language
English
Pages
32
File format
PDF
File size
532 KB
Published
18 October, 2026
Updated
18 October, 2026
MD5 checksum
CDF5DED5F810A871CC48C206BEA89941

About this manual

The Carrier Comfort System TEMP System is a communicating network of programmable thermostats designed to coordinate the operation of multiple single-zone heating and cooling units. The system uses a 3-wire shielded communication bus to link thermostats, allowing one unit with an electronic timeclock to broadcast time to the rest of the network. Each thermostat maintains independent occupied and unoccupied schedules and set points for its specific space.

What's inside

  • GENERAL
  • INSTALLATION
  • CONFIGURATION
  • TEMP SYSTEM THERMOSTAT DISPLAY
  • START-UP
  • COMMUNICATIONS
  • OCCUPIED MODE OPERATION
  • SENSORS
  • CONTROL OF HEATING AND COOLING EQUIPMENT
  • TROUBLESHOOTING PROCEDURES

Specifications

Wiring (Thermostat to Thermostat)18 gage, 3-conductor, shielded, stranded wire
Wiring (Thermostat to Relay Pack)18 gage, 5-conductor, shielded, stranded wire
Relay Pack Power24 vac/10 va
Relay Contact Max Load24 vac, 1 amp
Thermostat Location Heightabout 5 ft from the ground

Frequently asked questions

How many thermostats are required to have a timeclock in the system?

Only one thermostat per system is required to have a timeclock that will broadcast time to the rest of the system.

What is the maximum load of a relay contact?

The maximum load of a relay contact is 24 vac, 1 amp.