This manual provides installation, configuration, troubleshooting, and operational instructions for the Carrier TEMP System Unitary Controller Thermostat…
The Carrier Comfort System TEMP System is a communicating network of programmable thermostats designed to coordinate the operation of multiple single-zone heating and cooling units. The system uses a 3-wire shielded communication bus to link thermostats, allowing one unit with an electronic timeclock to broadcast time to the rest of the network. Each thermostat maintains independent occupied and unoccupied schedules and set points for its specific space.
| Wiring (Thermostat to Thermostat) | 18 gage, 3-conductor, shielded, stranded wire |
|---|---|
| Wiring (Thermostat to Relay Pack) | 18 gage, 5-conductor, shielded, stranded wire |
| Relay Pack Power | 24 vac/10 va |
| Relay Contact Max Load | 24 vac, 1 amp |
| Thermostat Location Height | about 5 ft from the ground |
Only one thermostat per system is required to have a timeclock that will broadcast time to the rest of the system.
The maximum load of a relay contact is 24 vac, 1 amp.