2012 is an input card for measuring mA or V signal or a potentiometer. The card can be plugged into the 2000 panel meter series, 2800 field meter series, 910E/920E large panel meter series, or 575F/1000F/1100F/ 1800F large field display series. The reading is displayed with six digits, if desired. Fixed trailing zeros are available. The card features a freely adjustable lowpass filter, hold function, and tare function. An external switch or relay contact can be used to trigger the hold and tare functions. 2012 supports several 2000 series auxiliary cards: an analog output card, a serial communications card, and two- or three- relay alarm cards. If the same device is equipped with two 2012 input cards, the combination is called 2212. It is possible to calculate a simple mathematical operation among the channels.
2012 is an input card for measuring an mA or V signal or a potentiometer. It can be plugged into the 2000 panel meter series, 2800 field meter series, 910E/920E large panel meter series, or 575F/1000F/1100F/1800F large field display series. The reading can be displayed with six digits, and fixed trailing zeros are available. The card includes a freely adjustable lowpass filter, hold function, and tare function; an external switch or relay contact can trigger hold and tare. It supports 2000 series auxiliary cards such as an analog output card, a serial communications card, and two- or three-relay alarm cards. If one device is equipped with two 2012 input cards, the combination is called 2212, and a simple mathematical operation can be calculated among the channels.
This manual covers connections, installation for the 2000, 2800, 910E/920E, and 1000F/1100F/1800F series, the user interface, the 2012 input card, and the 2000-OUT, 2000-RS, and 2000-RELx auxiliary cards, followed by technical specifications. Configuration can be done with the front or back panel display and buttons, via an RS-232 or RS-485 bus when a serial communications card is installed, or via the POL connector on the input card in slot A when no serial communications card is installed.
| Galvanic isolation | From outputs and supply voltage; two input cards share a common ground |
|---|---|
| Resolution | Not observable (24 bits) |
| Overvoltage limit | Not allowed above 120 VDC or 50 VAC with respect to ground |
| mA input resistance | Approx. 80 ohm |
| mA input range | 0…24 mA or wider |
| mA thermal drift | ±100 ppm/°C |
| V input resistance | 1.1 Mohm |
| V input range | 0…12 V or wider |
| V thermal drift | ±100 ppm/°C |
| Potentiometer resistance | 100 ohm…10 kohm |
| Potentiometer thermal drift | ±150 ppm/°C |
| Transmitter supply | 24 V ±20%, max 150 mA |
| Panel meter supply voltage (230 VAC model) | 85…260 VAC or VDC |
| Panel meter supply voltage (24 VDC model) | 12…32 VDC or 20…28 VAC |
| Panel meter power | Max 12 W; typ 3 W if transmitter supply not used and input card only |
| Panel meter protection class | 2 (reinforced insulation) |
| Panel meter operating temperature | -10…60°C |
| Panel meter IP class | IP65 front panel when gasket supplied is installed |
| Field meter supply voltage (230 VAC model) | 85…260 VAC or VDC |
| Field meter supply voltage (24 VDC model) | 12…32 VDC or 20…28 VAC |
| Field meter power | Max 12 W |
| Field meter protection class | 2 (reinforced insulation) |
| Field meter operating temperature | -10…60°C |
| Field meter IP class | IP65 |
It measures an mA or V signal or a potentiometer.
It can be plugged into the 2000 panel meter series, 2800 field meter series, 910E/920E large panel meter series, or 575F/1000F/1100F/1800F large field display series.
The combination is called 2212.
Yes, a simple mathematical operation can be calculated among the channels.