NXPLUS C type fixed-mount circuit breaker cabinet is a factory-assembled, type-tested, metal-enclosed, metal-armored, SF6-insulated indoor-mounted device, suitable for single-bus and double-bus systems. NXPLUS C type switchgear can be used in the following industrial substations: • power stations • power plants • cement industry • automobile industry • steel mills • rolling mills • mining industry • textile, paper and food industry • chemical industry • oil industry • pipeline equipment • marine equipment • power plants • petrochemical plants • shipbuilding industry • diesel power plants • emergency power supply equipment • open-pit brown coal mining • traction power supply equipment.
The NXPLUS C is a factory-assembled, type-tested, metal-enclosed, metal-clad, SF6-insulated indoor switchgear for single- and double-busbar systems, with fixed-mounted vacuum circuit breakers. The catalog covers cabinet types, typical applications, electrical data, switchroom layout, shipping data and dimensions.
It lists rated voltages from 7.2 to 24 kV at 50/60 Hz, busbar and feeder rated currents up to 2500 A, and short-time withstand and breaking currents of 31.5 kA or 25 kA depending on voltage. The document also describes vacuum circuit breakers, three-position switches, HRC fuse assemblies, busbars, current and voltage transformers, pressure-release channels, cable connections and standards. This manual is written in Chinese.
| Rated voltage | 7.2 / 12 / 15 / 17.5 / 24 kV |
|---|---|
| Rated frequency | 50 / 60 Hz |
| Rated short-time withstand current (3 s) | 31.5 kA (7.2–15 kV); 25 kA (17.5–24 kV) |
| Rated short-circuit breaking current | 31.5 kA (7.2–15 kV); 25 kA (17.5–24 kV) |
| Busbar rated current | 2500 A |
| Feeder rated current | 2500 A (7.2–15 kV); 2000 A (17.5–24 kV) |
| Width | 600 mm |
| Height | 2250 mm (600 mm cabinet); 2550 mm (900 mm cabinet) |
| Primary circuit protection degree | IP65 |
| Enclosure protection degree | IP 3XD |
| Expected service life | At least 35 years, up to 40 to 50 years |
The catalog states a maximum voltage of 24 kV.
It uses SF6 gas insulation.
It is suitable for single-busbar and double-busbar systems.
The document says it is maintenance-free in indoor environments.