This document introduces the features and advantages of the Perma-Span Expansion Tanks product series, including Drawn Steel Construction, Butyl Rubber Parabolic Diaphragm, In-Line Installation with or without Air Vent and Separator, Max. Working Pressure, Max. Temperature, Air Charge, etc.
This product leaflet details A.O. Smith’s Perma-Span expansion tanks designed for hydronic heating systems. It includes in-line and free-standing models with drawn steel construction and butyl rubber diaphragms. Tanks are pre-charged with air (12 PSI for PS series, 38 PSI for PSC series) and feature permanent air-water separation. Sizing charts are provided for residential and commercial applications, with models ranging from PS-2 to PS-86 and PSC-2X to PSC-86. The PSC series includes powder-coated interiors for potable water systems. Tanks are rated for max. 100 PSI or 150 PSI and max. 240°F.
Installation guidelines are included, such as placing tanks on the cold water supply side of water heaters and between the heater and backflow preventers. Contact information for engineering support and sizing assistance is provided for larger or custom systems.
| Max. Working Pressure | 100 PSI (PS series), 150 PSI (PSC-2X, PSC-5X, PSC-10X) |
|---|---|
| Max. Temperature | 240°F |
| Construction | Drawn Steel with Butyl Rubber Parabolic Diaphragm |
| Application | Hydronic Heating Systems (Residential and Commercial) |
The maximum temperature rating is 240°F for all models.
Use the sizing charts provided for finned tube baseboard radiation. For larger systems or different radiation types, contact the engineering department with system size, pressure, and temperature data.