This manual explains the function and use of the Intesis M-Bus slave
This user manual for the Intesis Modbus Slave – M-Bus gateway explains how M-Bus meters are integrated into Modbus RTU and/or Modbus TCP monitoring and control systems. It covers the M-Bus system, the gateway’s Modbus interface, connections, and the set-up process using Intesis MAPS.
The document lists gateway capacities for the 10, 20, 60, and 120 versions, including Modbus registers and M-Bus slave devices. It also provides M-Bus signal types, supported Modbus functions, address map and points definition, electrical and mechanical features, and dimensions.
| Type of Modbus Master devices | Modbus RTU (EIA485 or EIA232) and Modbus TCP |
|---|---|
| Number of Modbus Master devices | 1 Master device per RTU Node; up to 6 TCP connections |
| Number of Modbus registers | 250 / 500 / 1500 / 3000 depending on version |
| Number of M-Bus slave devices | 10 / 20 / 60 / 120 depending on version |
| Number of M-Bus signals | 250 / 500 / 1500 / 3000 depending on version |
| M-Bus baud rate | Configurable from 300 to 9600 bps |
| M-Bus connection | EIA485 two wires |
It integrates M-Bus meters into Modbus RTU and/or Modbus TCP monitoring and control systems.
No. The gateway has an embedded level converter and can connect directly to M-Bus devices without extra hardware.
Configuration is carried out using the configuration software Intesis MAPS.
The 120 version supports 120 M-Bus slave devices.