IntesisBox® Modbus Server LON User Manual is an instruction manual for the IntesisBox® Modbus Server LON product produced by Intesis Software S.L.
This document describes the IntesisBox Modbus Server LON gateway, which integrates LON-based systems into Modbus-enabled systems (SCADA, BMS, PLC). The device acts as a LON client to read/write points from LON devices and exposes them via its Modbus interface (RTU or TCP). It supports three models: Tiny (100 datapoints), Basic (500 datapoints), and Extended (3000 datapoints).
| Supported LON Topology | Free Topology channel (FT-10) |
|---|---|
| Tiny Model Datapoints | 100 |
| Basic Model Datapoints | 500 |
| Extended Model Datapoints | 3000 |
| Tiny Model LON Devices | 64 |
| Extended Model LON Devices | 128 |
| Modbus RTU Baud Rates | 1200, 2400, 4800, 9600, 19200, 38400 and 56700 |
| Modbus Data Bits | 8 |
It integrates LON systems into Modbus (RTU and TCP) systems by acting as a LON device that reads/writing points from other LON devices and offering them via its Modbus interface.
No, only one Modbus Mode can be active simultaneously, either Modbus RTU or Modbus TCP.
Functions 03 and 04 are used for reading, while functions 06 and 16 are used for writing Modbus registers.