This document introduces the function and characteristics of IntesisBox® Modbus Server LON, including system composition, installation and configuration, function introduction, etc.
The IntesisBox Modbus Server LON is a gateway designed to integrate LON (LonWorks) systems into Modbus-enabled systems such as SCADA, BMS, or PLCs. It acts as a LON client device that continuously polls LON devices to read points and offers these values via its Modbus interface. Conversely, it can write values to LON devices when receiving write requests from a Modbus master.
| Supported LON topology | Free Topology channel (FT-10) |
|---|---|
| Tiny version datapoints | 100 |
| Basic version datapoints | 500 |
| Extended version datapoints | 3000 |
| Tiny version LON devices | 64 |
| Extended version LON devices | 128 |
| Modbus RTU Baud rates | 1200, 2400, 4800, 9600, 19200, 38400 and 56700 |
| Modbus register sizes | 2 bytes (16 bits) or 4 bytes (32 bits) |
A typical application is the integration of Daikin VRV Air Conditioners into a Modbus enabled system like SCADA or BMS.
No, IntesisBox is a LON client device and no LON points of IntesisBox can be accessed from other LON devices connected to the LON network.
Modbus functions 03 and 04 (read holding registers and read input registers) can be used to read Modbus registers.