About this manual

The Elma TOHM-E is a portable socket and earth loop tester designed for use with 230 V AC single-phase 2-pole + earth "Danish" K-type power sockets. It is intended for qualified operators to test power sockets, measure earth electrode impedance, and measure phase-neutral voltage in TT earthing systems. The device features a rotating plug for ergonomic handling and displays various indications regarding voltage, impedance, and wiring faults.

What's inside

  • Connecting
  • Indications of Tohm-e
  • Impedance Measurement
  • Power Socket and Earth OK
  • Phase and Neutral Reversed
  • Not Wired to Earth
  • Earth Not Correct
  • Safety and Specifications
  • Accuracy
  • Use

Specifications

Compatible Power Sockets230 V AC single-phase 2-pole + earth "Danish" K-type power sockets
Earth Electrode Impedance Range0.0 Ω to 2000 Ω
Earth Electrode Impedance Threshold500 Ω
Operating Temperature-20 °C to +40 °C
Mains Supply Voltage230 V~ - 240 V~
Current18 mA~
Protection ClassClass 2

Frequently asked questions

What is the OK/not OK threshold for earth electrode impedance?

The threshold is 500 Ω. If the impedance is below this value, it is considered OK.

Is the TOHM-E compatible with 30 mA RCDs?

Yes, the device is compatible with 30 mA~ RCDs and uses a low current of 18 mA~.

Can the TOHM-E be used as a voltage detector?

No, the manual explicitly states that Tohm-e is not a voltage detector and should not be used for that purpose.

What is the accuracy of the earth electrode impedance measurement?

The accuracy is ±0.7 Ω from 0.0 Ω to 19.9 Ω, ±6.1 Ω from 20.0 Ω to 99.9 Ω, and ±7.0 Ω from 100 Ω to 999 Ω.