This document is the user manual of TOHM-E product, which introduces the features and usage methods of the product.
The Elma TOHM-E is a portable socket and earth loop tester designed for use with 230 V AC single-phase 2-pole + earth "Danish" K-type power sockets. It is intended for qualified operators to test power sockets, measure earth electrode impedance, and measure phase-neutral voltage in TT earthing systems. The device features a rotating plug for ergonomic handling and displays various indications regarding voltage, impedance, and wiring faults.
| Compatible Power Sockets | 230 V AC single-phase 2-pole + earth "Danish" K-type power sockets |
|---|---|
| Earth Electrode Impedance Range | 0.0 Ω to 2000 Ω |
| Earth Electrode Impedance Threshold | 500 Ω |
| Operating Temperature | -20 °C to +40 °C |
| Mains Supply Voltage | 230 V~ - 240 V~ |
| Current | 18 mA~ |
| Protection Class | Class 2 |
The threshold is 500 Ω. If the impedance is below this value, it is considered OK.
Yes, the device is compatible with 30 mA~ RCDs and uses a low current of 18 mA~.
No, the manual explicitly states that Tohm-e is not a voltage detector and should not be used for that purpose.
The accuracy is ±0.7 Ω from 0.0 Ω to 19.9 Ω, ±6.1 Ω from 20.0 Ω to 99.9 Ω, and ±7.0 Ω from 100 Ω to 999 Ω.