This file provides information on troubleshooting for the Veeder-Root EMR3 system.
This EMR3 Troubleshooting Guide (Manual No. 577014-010, Revision A) from Veeder-Root explains how to test an EMR3 system and interpret its display messages. It covers display head self-diagnostic checks, LCD display tests, pulse encoder input checks, and printer checks.
The guide lists EMR3 informational messages and delivery, startup, system, relay setup, and calibration error codes, including causes and corrective steps. It also describes the IB tri-color LED indicator lamp and includes an appendix with a production release schedule for EMR3 software.
| Maximum encoder speed | 1000 rpm |
|---|---|
| Thermoprobe resistance at 25 degrees Celsius | About 10 K ohms |
| Display Head self-test duration | About 25 to 80 seconds |
| Message descriptor field length | 14 characters |
Cycle power by turning the power off for at least 20 seconds, then turn it on again. Each Display Head tests its own circuit board hardware during power up, which takes about 25 to 80 seconds.
The maximum speed is 1000 rpm. If the shaft speed exceeds the Display Head Processor capability, reduce the flow rate or add a mechanical gear reduction and calibrate the meter.
At 25 degrees Celsius, an ohmmeter should read about 10 K ohms. If it does not, replace the Thermoprobe.
The ticket printer is busy processing the current request. After printing, replace the printed ticket with a new ticket before printing another.