Anderson Instrument Co. TDL Differential Level Transmitter Instruction Manual

This manual describes the features and characteristics of the TDL differential level transmitter, including installation, connection, calibration, etc.


Anderson Instrument Co. TDL Differential Level Transmitter Instruction Manual - cover page
Brand
Anderson Instrument Co.
Category
Industrial Supply
Document type
User Manual
Language
English
Pages
46
File format
PDF
File size
1.7 MB
Published
19 October, 2023
Updated
19 October, 2023
MD5 checksum
0A0942A064F7E02E055819B5899DE166

About this manual

The Anderson Instrument Co. TDL Differential Level Transmitter is designed to measure liquid level in vessels under positive pressure or vacuum conditions. It utilizes dual sensors placed at the bottom and top of the vessel to calculate a true level output, providing a primary 4-20 mADC signal proportional to the product height and a secondary signal for pressure or vacuum conditions. The unit is available with HART communication compatibility for digital setup and configuration via a handheld terminal.

What's inside

  • Product Description and Specifications
  • Pre-Installation and Mounting
  • Wiring
  • Initial System Startup
  • Operation
  • Configuration
  • Calibration
  • HART Communication Operation
  • Troubleshooting
  • Parts and Accessories

Specifications

Primary Output Signal4-20 mADC
Secondary Output Signal4-20 mADC
Transmitter Enclosure Power18-30 VDC, 92mA
Loop Power Requirement12-30 VDC, 25mA
Cable Recommendation18-24 AWG, 2 conductor, with ground, shielded and PVC coated
Transmitter Housing Material304 Stainless Steel
Calibrated Accuracy±0.25% of URL
Process Temperature Limits0°- 300°F (-18°-149°C)

Frequently asked questions

What is the primary function of the TDL transmitter?

It measures liquid level in vessels where the condition inside is at a positive pressure or a vacuum, referenced to atmosphere.

How does the TDL calculate the true level output?

It uses dual sensors, one at the bottom and one at the top of the vessel, to calculate the differential between the two probes regardless of pressure or vacuum conditions.

Is the TDL compatible with HART communication?

Yes, the TDL may be specified as HART compatible, allowing setup and configuration via a handheld terminal.

What are the ambient temperature limits for the sensor only?

The ambient temperature limits for the sensor only are 15°- 120°F (-9°-48°C).