This manual describes the features and characteristics of the TDL differential level transmitter, including installation, connection, calibration, etc.
The Anderson Instrument Co. TDL Differential Level Transmitter is designed to measure liquid level in vessels under positive pressure or vacuum conditions. It utilizes dual sensors placed at the bottom and top of the vessel to calculate a true level output, providing a primary 4-20 mADC signal proportional to the product height and a secondary signal for pressure or vacuum conditions. The unit is available with HART communication compatibility for digital setup and configuration via a handheld terminal.
| Primary Output Signal | 4-20 mADC |
|---|---|
| Secondary Output Signal | 4-20 mADC |
| Transmitter Enclosure Power | 18-30 VDC, 92mA |
| Loop Power Requirement | 12-30 VDC, 25mA |
| Cable Recommendation | 18-24 AWG, 2 conductor, with ground, shielded and PVC coated |
| Transmitter Housing Material | 304 Stainless Steel |
| Calibrated Accuracy | ±0.25% of URL |
| Process Temperature Limits | 0°- 300°F (-18°-149°C) |
It measures liquid level in vessels where the condition inside is at a positive pressure or a vacuum, referenced to atmosphere.
It uses dual sensors, one at the bottom and one at the top of the vessel, to calculate the differential between the two probes regardless of pressure or vacuum conditions.
Yes, the TDL may be specified as HART compatible, allowing setup and configuration via a handheld terminal.
The ambient temperature limits for the sensor only are 15°- 120°F (-9°-48°C).