SL/SX LEVEL TRANSMITTER INSTRUCTION MANUAL
This document is the instruction manual for the Anderson Instrument Co. SL/SX Liquid Level Transmitter. It covers the general description, intended use, and technical specifications of the device. The manual details the proper installation procedures, including tank shell installation and atmospheric venting, as well as electrical wiring requirements for the field-wireable connector assembly.
| Output Signal | 4-20 mA |
|---|---|
| Cable Requirements | 2 conductor, stranded, 18-24 AWG, shielded with ground |
| Cable Sheath Size | 4-8mm (0.16-0.31") |
No, do not remove the sensor from the process while it is operating as this can contaminate the process and cause human injury.
This unit accepts DC voltage only, between 12-40 VDC.
The sensor outputs 4.00 mA when the vessel is empty.
The maximum calibration value for SL3/SL7 or SX7 models is 835.