This document is the instruction manual of the HA Sanitary Electronic Pressure Transmitter, produced by Anderson Instrument Co. Inc., which introduces the specifications, installation, maintenance and other contents of the product
This manual provides step-by-step instructions for installing, wiring, calibrating, and troubleshooting the Anderson HA Sanitary Electronic Pressure Transmitter. It covers specifications, sensor and instrument wiring, loop power requirements, zero and span adjustments, and troubleshooting common issues like voltage or current faults. The document emphasizes moisture protection and proper mounting to ensure sensor reliability.
The transmitter outputs a 4-20 mA signal and is designed for sanitary applications with 316L stainless steel wetted parts. Calibration procedures are detailed, including formulas for calculating expected mA output based on pressure range and using reference gauges and multimeters.
| Excitation | 10-40 VDC (Absolute), 24 VDC Nominal regulated or unregulated |
|---|---|
| Output | 4-20 mA DC, 2 wire with non-interrupting circuit verification test points |
| Loop Resistance | 0-700 ohms at 24 VDC |
| Accuracy | ± 0.5% of Full Scale |
| Repeatability | ± 0.3% of full scale |
| Hysteresis | ± 0.25% of full scale |
| Linearity | ±0.10% of full scale |
| Stability | ±.25% of calibrated range/6 months |
| Storage Temperature | -40° to 149°F (-40°C to 65°C) |
| Process Temperature Limits | 30 to 300°F (-1°C to 149°C) (Horizontal Mount recommended over 275°F) |
| Ambient Temperature Limits | 40 to 120° F (4 to 49°C) |
| Effect of Temperature Change | ± 0.1 psig/10°F typical |
| Over-Range Rating | 2 times base range |
| Wetted Parts | 316L stainless steel electropolished (Ra max. = 8 microinches, .2 microns) |
| Housing Material | 304 Stainless Steel |
Anderson recommends a 24 gauge, 4 conductor, shielded cable (Belden #9534 or equivalent).
The HA transmitter outputs a 4-20 mA DC signal, 2 wire with non-interrupting circuit verification test points.