Phasetronics EZ3 SCR Power Controller Operation and Service Manual

This document is an operation and service manual for EZ3 series SCR power controllers. It introduces the basic functions and features of the controller, as well as the wiring method, start-up procedure, etc.


Phasetronics EZ3 SCR Power Controller Operation and Service Manual - cover page
Brand
Phasetronics
Category
Industrial Robot
Document type
Service Manual
Language
English
Pages
18
File format
PDF
File size
1.9 MB
Published
19 October, 2023
Updated
19 October, 2023
Model
EZ3
MD5 checksum
197C07F2745864D60CCC4EE7E4BFCDD5

About this manual

This manual provides detailed instructions for operating and servicing Phasetronics EZ3 SCR power controllers, covering manual and automatic control setups, wiring, specifications, and start-up procedures. It includes information on mounting, power connections, jumper settings, and replacement parts for various amp ratings. The manual also addresses safety precautions and warranty terms.

What's inside

  • Introduction
  • Specifications
  • Connections
  • Start-up Procedure
  • Dimensions
  • Appendix: Connectors, Jumpers, Replacement Parts, Model Selection Guide
  • Warranty Information

Specifications

Output Voltage0 to 100%
AC Supply Voltage120/208/240/380/415/480/575 Vac (+10% to -15%, 50/60 Hz)
Ambient Temperature0 to 40 degrees C (32 degrees F to 104 deg. F)
SCR Peak Inverse Voltage (PIV Rating)1600V for units up to 100A, 1800V for units 150A to 1000A
CoolingConvection cooling through 150A. Fan cooled at 225A and above.

Frequently asked questions

What is the output voltage range of the EZ3 controller?

The output voltage range is 0 to 100%.

What are the supported AC supply voltages?

Supported AC supply voltages are 120/208/240/380/415/480/575 Vac (+10% to -15%, 50/60 Hz).

What is the ambient temperature operating range?

The ambient temperature operating range is 0 to 40 degrees C (32 degrees F to 104 deg. F).

What is the SCR Peak Inverse Voltage (PIV) rating for different amp ratings?

Units up to 100A have a PIV rating of 1600V, and units from 150A to 1000A have a PIV rating of 1800V.