Motortronics MVC Plus 10-13.8 kV Class Variable Frequency Drive User Manual

This manual introduces the overview, specifications, design features, working principle, general protection, thermal overload protection, firing circuit, electronics, etc. of the MVC Plus 10-13.8 kV class variable frequency drive product.


Motortronics MVC Plus 10-13.8 kV Class Variable Frequency Drive User Manual - cover page
Brand
MOTORTRONICS
Category
Industrial Robot
Document type
User Manual
Language
English
Pages
79
File format
PDF
File size
1.8 MB
Published
19 October, 2023
Updated
19 October, 2023
MD5 checksum
D55FCCBFC9B3CEB8D5F178F2C2D5BFF7

About this manual

This manual covers the setup, operation, and maintenance of the Motortronics MVC Plus 10-13.8 kV Class variable frequency drive. It includes wiring diagrams, control connections, menu navigation, setpoint programming, metering functions, and troubleshooting. The device is an SCR-based controller for medium voltage AC motors, with programmable overload curves, phase imbalance protection, and communication via Modbus RTU. Maintenance sections detail SCR testing and failure analysis.

What's inside

  • Introduction
  • Connections
  • Start-Up
  • User Interface and Menu Navigation
  • Setpoint Programming
  • Metering Pages
  • Maintenance and Troubleshooting

Specifications

AC Supply Voltage10000 – 13800 VAC +10 to – 15% (Model dependent)
Unit Running Overload Capacity125% - Continuous 500% - 60 seconds, 600% - 30 seconds
Frequency50 or 60Hz, +2Hz hardware selectable
SCR Peak Inverse Voltage Ratings27000V - 39000V (Model dependent see Table 1)
Control Voltage120VAC (Customer supplied)
Auxiliary ContactsMultiple: Form C (Contacts), rated 5 Amps, 240VAC max. 8 Relays (4 programmable): Form C contacts
BIL Rating110kV
Overload ResetManual Retentive Thermal Memory
Phase Current Imbalance ProtectionImbalance Trip Level: 5 - 30% current between any two phases
Over Current ProtectionTrip Level: 100 - 300% of motor FLA
Load Loss Trip ProtectionUnder Current Trip Level: 10 -90 % of motor FLA
Coast Down Lockout TimerCoast Down Time Range: 1 - 60 minutes
Starts-per-hour Lockout TimerRange: 1 - 6 successful starts per hour
Operator InterfaceLCD Readout Alpha numeric LCD display
Serial CommunicationsModbus RTU Signal RS-485, RS-422 or RS232
Clock and MemoryReal Time Clock Lithium ion battery for clock memory only

Frequently asked questions

What is the AC supply voltage range for the MVC Plus?

10000 – 13800 VAC +10 to – 15% (Model dependent).

What is the phase current imbalance protection trip level?

5 - 30% current between any two phases.

What is the serial communication protocol?

Modbus RTU Signal RS-485, RS-422 or RS232.