This is an installation manual for VMX-agilityTM soft starters, which includes installation methods, safety precautions, etc.
This document provides detailed installation instructions for Motortronics VMX-agility soft starters, including mounting requirements, enclosure ventilation, altitude derating, and electrical connections. It also covers safety warnings, environmental specifications, and accessory installation. The guide is intended for qualified personnel and includes technical details for proper installation and operation in industrial environments.
The manual includes sections on horizontal mounting, environmental ratings, and specific accessories like remote keypads and cooling fans. It also addresses safety hazards, such as dangerous voltages, and provides formulas for calculating ventilation requirements based on heat dissipation.
| Heat Output (Model 101) | 9 W |
|---|---|
| Weight (Model 101) | 1.97 kg [4.20 lb] |
| Ambient Operating Temperature | -20°C to 40°C; above 40°C derate linearly by 2% per °C to max 60°C |
| Maximum Altitude | 1,000m; above 1000m derate by 1% per 100m to max 2,000m |
Above 40°C, derate linearly by 2% per °C to a maximum of 60°C (140°F).
Mount to a flat, vertical surface using mounting holes on the base-plate. Ensure the 'TOP' is uppermost unless horizontally mounted.
Q = (4 x Wt / (Tmax-Tamb)) where Q is air delivery in m³/h, Wt is heat in Watts, Tmax is max enclosure temperature, Tamb is air entry temperature.