Motortronics DXT Series 39-1250A Digital Solid State Soft Starter Installation & Operation Manual

This manual describes the installation and operation of the DXT Series 39-1250A Digital Solid State Soft Starter.


Motortronics DXT Series 39-1250A Digital Solid State Soft Starter Installation & Operation Manual - cover page
Brand
MOTORTRONICS
Category
Motor
Document type
User Manual
Language
English
Pages
89
File format
PDF
File size
744 KB
Published
19 October, 2023
Updated
19 October, 2023
MD5 checksum
1A5E3115BF232EBAE073F8FC08FA7A92

About this manual

The DXT Series is a high-end digitally programmable solid state reduced voltage soft starter designed for three-phase AC induction or synchronous motors. It provides stepless soft starting to protect mechanical components from excessive torque stress and electrical systems from high inrush currents. The unit features advanced motor and load protection, including retentive thermal memory, dynamic reset capacity, and true thermal modeling, all built-in as standard features.

What's inside

  • Introduction
  • Specifications
  • Theory of Operation
  • Installation
  • Start-Up
  • User Interface and Menu Navigation
  • Setpoint Programming
  • Metering Pages
  • Maintenance and Troubleshooting

Specifications

Type of LoadThree phase AC induction motors or synchronous motors
AC Supply Voltage208 - 600 VAC +10%, 50/60 Hz
HP Ratings10 - 1125 HP
Unit Overload Capacity125% - Continuous, 500% - 60 seconds, 600% - 30 seconds
Cooling MethodConvection up to 180A, fan assisted 62 - 120A, Fan ventilated 220 - 1250A
Ambient Condition (Chassis)0° to 50 °C (32° to 122°F)
ProtocolModbus RTU
Signal TypeRS-485, RS-422 or RS232

Frequently asked questions

What types of motors is the DXT Series soft starter compatible with?

The DXT Series is compatible with three-phase AC induction motors or synchronous motors.

What is the maximum horsepower rating for the DXT Series 39-1250A?

The unit supports ratings up to 1125 HP.

Does the DXT Series include a bypass contactor?

Yes, a shunt rated contactor is included as standard in all NEMA 12 enclosed units 92A and above.