This manual describes how to install refrigerant piping for small split cooling and heat pump systems, including spine fin units, microchannel units, and high rise systems.
This manual guides the selection of liquid and suction lines for split cooling and heat pump systems using Trane and American Standard equipment. It includes tables and charts for sizing lines based on refrigerant type, system capacity, and line length. Key design principles focus on minimizing pressure drop, ensuring oil return, and maximizing system reliability. The guide also covers high-rise applications and refrigerant handling.
The manual recommends using the Windows-based piping program for accurate calculations and includes detailed specifications for liquid and suction line diameters, pressure drops, and refrigerant charge adjustments.
| Refrigerant Type | R-410A and R-22 |
|---|---|
| Maximum Liquid Line Pressure Drop | 50 PSI |
| System Capacity Range | 1.0 to 5.0 tons nominal |
| Recommended Suction Line Size | Largest diameter listed for given tonnage |
The maximum allowable pressure drop for R-410A liquid lines is 50 PSI.
The manual covers R-410A and R-22 refrigerants.
Suction lines should be sized as large as possible while still maintaining sufficient velocity for oil return.