About this manual

The KUTAI ATS-380 is a microprocessor-based automatic transfer switch controller designed to monitor normal and standby power sources. It ensures the transfer of electrical loads between sources based on preset voltage and frequency settings, initiating generator starts if the normal source fails. The unit is a compact, panel-mounted device that replaces traditional relay logic panels.

What's inside

  • Introduction
  • Hardware Description
  • Operator Panel
  • Operation
  • Installation Instructions
  • Typical Wiring
  • Functions and Features
  • Safety Precautions

Specifications

System Voltage280 VAC to 480 VAC
Frequency50 or 60 Hz
Adjustable Over voltage range390VAC ~ 480VAC
Adjustable Under voltage range280VAC ~ 370VAC
Adjustable Over frequency range51Hz ~ 70Hz
Adjustable Under frequency range40Hz ~ 59Hz

Frequently asked questions

What is the adjustable range for the Time Delay Normal to Emergency (TDNE)?

The adjustable TDNE range is 0 to 60 seconds (0 to 300 sec).

Can the ATS-380 perform a time delay engine start function without control power?

Yes, the controller can perform this function without control power for 30 seconds.

Does the ATS-380 require a PC connection for programming?

No, there is no need for a PC connection; all changes can be made in the field.