This manual introduces the basic functions and use methods of Kutai TCS4P125 Automatic Transfer Switch Control Unit (hereinafter referred to as TCS4P125).
This manual covers the installation, operation, and maintenance of the TCS4P125 Automatic Transfer Switch Control Unit (TC-V2) designed for 3 Phase 4 Wire systems. The unit is intended for qualified personnel and includes safety precautions regarding high voltages.
| Rated Voltage | 250 Vac |
|---|---|
| Rated Current | 125 Amps |
| Number of Poles | 4P |
| Coil Operating Voltage | 110 / 220 Vac +/- 20% |
| Operating Temperature | -20 to +60 ˚C |
| Operating Humidity | 0 to 95% |
| Weight | 2.0 kg +/- 2% |
TDNE provides a time delay when transferring from Normal to Emergency, adjustable from 0 to 99 seconds.
To enter programming mode, push and hold the Program button for 10 seconds until the screen displays the version and programming sequence begins.
It provides for automatic test operation of the generator at a fixed interval of once per 1 to 4 weeks with a specific test day and time.