This manual describes the installation, operation, and maintenance of the KFPC1-F07-DN controller.
This manual provides instructions for installing, configuring, and operating the KFPC1-F07-DN controller, which controls proportional valves using PWM signals. It includes safety precautions, signal input settings, and detailed steps for initial calibration using potentiometers and switches. The controller supports 4-20mA or 0-10V inputs and features temperature compensation and current monitoring.
The manual emphasizes safety, proper installation, and initial setup procedures to ensure correct valve operation. It includes tables for reference values and step-by-step methods for adjusting current thresholds using MIN and MAX potentiometers, with options for internal or external signal input calibration.
| Mounting type | DIN rail mounting type |
|---|---|
| Power supply voltage | DC24V |
| Ambient temperature range | 0 to 50°C (no condensation allowed) |
| Maximum allowable load current | 1.1 A |
| Monitor signal | Directly proportional to the solenoid current, 1mV = 1mA |
| RAMP response time | 0 to 10 seconds |
The maximum allowable load current is 1.1 A.
Use potentiometer MIN to adjust the current value I1 at which the valve starts to open, following the procedure in section 6-1-3.
The RAMP response time can be adjusted from 0 to 10 seconds using the potentiometer RAMP.