This manual describes the principles of operation and provides installation instructions and a parts list for the Type 289RC exhaust booster.
This manual provides detailed instructions for installing, operating, and maintaining the Type 289RC exhaust booster, a device used to provide 'release control (RC)' pressure to pneumatic systems. It includes specifications, connection diagrams, calibration procedures, and maintenance steps. The unit requires no field adjustment and is designed for rapid response in systems like compressor surge valves. Maintenance involves replacing elastomer parts and recalibrating after disassembly.
| Body Size | 1 NPT Inlet and Outlet Connections |
|---|---|
| Maximum Pressure | 100 psig / 6.9 bar |
| Dead Band | 0.5 psid / 0.034 bar d |
| Exhaust Flow Capacity | C v = 22 |
| Temperature Capabilities | -20 to 180°F / -29 to 82°C |
| Approximate Weight | 4 lbs / 2 kg |
No, the adjusting screw is factory set and must not be changed.
The dead band is 0.5 psid / 0.034 bar d pressure across the bypass valve.
Mounting is recommended with the outlet exhaust connection pointing down.