This file is a maintenance manual that mainly introduces the maintenance methods and maintenance precautions of the 3900 water purifier model
The Model 3900 is a commercial water conditioner designed for water softening applications. The manual outlines pre-installation requirements, including water pressure specifications (minimum 25 psi, maximum 120 psi) and electrical needs (115 volt, 60 Hertz). It details the flow diagrams for various operational positions such as Service, Backwash, Brine, Slow Rinse, Rapid Rinse, and Brine Tank Refill.
| Water Pressure (Minimum) | 25 pounds |
|---|---|
| Water Pressure (Maximum) | 120 p.s.i. |
| Water Temperature (Maximum) | 110 °F |
| Electrical Supply | 115 volt, 60 Hertz |
| Drive Motor Voltage | 115 V. 60 Hz. |
A minimum of 25 pounds of water pressure is required for the regeneration valve to operate effectively.
The unit requires a continuous 115 volt, 60 Hertz current supply.
The unit cannot be subjected to water temperatures exceeding 110 °F.