Elma 8410 is an instrument for safely determining socket connections. It can be used to check if phase and zero are correctly connected, as well as test the protective HPFI relay.
This user manual provides instructions for safely operating and maintaining the Elma 8410 socket connection tester. It covers proper usage, safety precautions, testing procedures, and technical specifications. The device is designed to verify correct socket wiring, test 30mA RCDs, and detect PE faults. Maintenance is minimal, requiring only cleaning with a damp cloth and avoiding direct sunlight.
| Nominal Voltage | 230V AC (± 10 %) |
|---|---|
| Frequency | 50…60 Hz |
| Measurement Category | CAT III / 300 V |
| Contamination Degree | 2 |
| Operating Altitude | up to 2000 m |
| Contact Voltage Threshold | > 50 V |
| RCD Test Time | 60…300 ms |
| RCD Test Current | 30 mA (± 15 %) |
| Temperature Range | 0°…40°C |
| PE Fault Threshold | > 50 V to ground without touching the contact probe |
| Max. UUT Capacitance | 0,1 μF |
It tests socket wiring, verifies correct phase and neutral connections, and checks if the RCD (residual current device) is working correctly.
Connect the device to a socket, touch the contact probe, and read the results on the LCD or LEDs. Ensure the installation is powered off before testing.