This manual explains the RS485 communication function of the TOSVERT VF-S15 series.
This instruction manual explains the RS485 communication interface function provided for the TOSHIBA TOSVERT VF-S15 series of industrial inverters. It covers data transmission specifications, including baud rates, parity settings, and frame synchronization requirements.
The document details two supported communication protocols: the Toshiba inverter protocol and the Modbus RTU protocol. It provides specific instructions on command formats for reading and writing parameters, monitoring operating status (such as output frequency and current), and controlling operations remotely via a computer or controller.
| Transmission scheme | Half-duplex (Standard) |
|---|---|
| Communication baud rate | 9600/19200/38400 bps |
| Character transmission format (ASCII) | JIS X 0201 8-bit |
| Frame length | Variable |
The inverter supports the Toshiba inverter protocol and the Modbus RTU protocol.
An interval corresponding to at least 3.5 bytes of data must be placed between frames.
The user selects the desired protocol using parameter F824 (Communication Number).