This document describes the normal working conditions and installation conditions of the fuse, including environmental temperature, atmospheric conditions, pollution level, installation category, and installation conditions. It also provides information on the parameters and technical performance of the fuse support base.
This document provides the user manual for the CHINT NRT28 series cylinder cap fuse support base. It covers normal operating and installation conditions, including environmental temperature, atmospheric conditions, pollution degree, and altitude correction factors.
The manual also lists the main technical parameters and dimensions for various models (NRT28-32, NRT28-63, NRT28-125), specifies the compatible fuse bodies, and provides ordering instructions and examples. This manual is written in Chinese.
| Rated Voltage | Up to 500V |
|---|---|
| Rated Current | Up to 125A |
| Frequency Range | 45Hz~62Hz |
| Pollution Degree | 3 |
| Maximum Ambient Temperature | 40°C |
| Minimum Ambient Temperature | -5°C |
| Breaking Capacity | 100kA |
No, this type of fuse is not recommended for capacitor cabinets; RT36 type is suggested as a replacement.
The maximum operating temperature is 40°C.
The minimum ambient air temperature is -5°C.
The rated voltage is 500V.