This document introduces a wireless three-phase current meter and light sensor named R718NL37. The product adopts LoRa technology and is compatible with LoRaWAN protocol. It features the use of open-close current transformers and built-in light sensors. It can be widely used in indoor current detection devices in homes, hotels, office buildings, shopping malls, etc., as well as environments that require adjusting lighting brightness or current intensity based on light intensity.
The NETVOX R718NL37 is a wireless sensor designed to detect input current in three-phase AC power and ambient light intensity. It utilizes LoRaWAN technology with an integrated SX1276 module to transmit data to a gateway for monitoring and remote control via cloud platforms. The device operates on a battery power supply and includes a built-in light sensor for environmental monitoring.
| Wireless Module | SX1276 |
|---|---|
| Power Supply | 2 ER14505 batteries (3.6V/2200mAh) |
| Battery Life | 5 years |
| Sleep Current | 32uA |
| Wake-up Current | 7mA |
| RF Receive Current | [email protected] |
| RF Transmit Current | [email protected] |
| Current Measurement Error | <+-1% |
| Current Resolution | 1mA |
| Current Measurement Range | 1A~75A |
| Frequency Range | 863MHz-928MHz, 470MHz-510MHz |
| Power Output | 19dBm±1dBm |
| Receive Sensitivity (LoRa) | -136dBm |
| Communication Distance | 10km |
| Data Transmission Rate | 0.3kbps~50kbps |
| Modulation Mode | LoRa/FSK |
| Supported LoRaWAN Regions | EU863-870, US902-928, AU915-928, KR920-923, AS923, CN470-510 |
| Rated Primary Input Current | 30A |
| Rated Secondary Output Current | 10mA |
| Saturation Current | ≥75A |
| Turns Ratio | 3000:1 |
| Load Resistance | 10Ω |
| Insulation Voltage | 3000V |
| Light Sensor Model | TSL45315 |
| Light Intensity Range | 3LUX-220KLUX |
| Light Intensity Accuracy | <15% |
| Communication Interface | I2C |
| Operating Temperature | -40℃~+85℃ |
The device is compatible with the LoRaWAN protocol.
The battery life is 5 years under specific conditions (25°C, 30min report frequency, 20dBm tx power, SF=10).
The current measurement error is less than ±1%.
The communication distance is 10km in a clear line of sight without obstacles.