ANALOG DEVICES AN-641 handbook

This is an application note about ADE7752


ANALOG DEVICES AN-641 handbook - cover page
Brand
Analog Devices
Category
Other Electronics
Document type
Application Note
Language
English
Pages
16
File format
PDF
File size
496 KB
Published
02 August, 2012
Updated
30 September, 2023
Model
ADE7752
MD5 checksum
4F9702F4E696006DAE32266404023568

About this manual

The document details a reference design for a Class 1 meter intended for use in Wye-connected 3-phase, 4-wire distribution systems. It meets IEC 61036 and Indian Standards IS 13779-99 accuracy requirements, achieving less than 0.1% error over a 500:1 current dynamic range for balanced loads.

The design utilizes the ADE7752 single-chip solution which includes analog-to-digital converters and digital signal processing. Key features include differential output drivers for electromechanical counters, high-frequency pulse outputs for calibration, and logic outputs to indicate negative active power or miswiring.

What's inside

  • Introduction
  • Design Goals
  • Accuracy Requirements
  • Detailed Description
  • Front End Networks
  • Calibration Network
  • Power Supply
  • Energy Calculation
  • Negative Power Detection
  • Design Equations

Specifications

Accuracy ClassClass 1
Current Dynamic Range500:1
Maximum Current per Phase50 A
Meter Constant100 impulses/kWh
Line Voltage to Neutral240 V
Startup Current13.75 mA
No-Load Threshold3.3 W

Frequently asked questions

What accuracy class does this meter design meet?

The design meets the IEC 61036 Class 1 meter accuracy requirement.

What is the maximum current per phase for this design?

The meter was designed for a maximum current of 50 A per phase.

How is the calibration process sped up?

A high frequency output at the CF pin is used, which is calibrated to 1600 impulses/kWh.

Download PDF (496 KB)

More Analog Devices Manuals